Motor full-load current chart

Typical full-load amps for 4-pole induction motors at 400 V and 415 V three-phase and 230 V and 240 V single-phase. Use the calculator above the chart to go straight from motor size to cable size.

For estimating purposes only. Results are indicative. Final selections must be confirmed by a qualified person for the actual installation and conditions.

FreeNo loginNo watermark

1  The load

Starting method

2  The cable

3  Installation and run

4  Protection optional

The MCB sets the earth fault loop length check (loop impedance at 80% of nominal voltage). Fault level and clearing time set the short-circuit check.

Results are indicative estimates for planning only and must be checked by a qualified person. Read the calculator disclaimer.

Three-phase motors, 400 V and 415 V

Typical 4-pole motors. Always use the nameplate current where you have it.

Full-load current (A), three-phase
Motorhp400 V415 V
0.37 kW0.51.11.1
0.55 kW0.71.51.4
0.75 kW1.01.91.8
1.1 kW1.52.62.5
1.5 kW2.03.43.3
2.2 kW3.04.94.7
3 kW4.06.56.3
4 kW5.48.58.2
5.5 kW7.411.511.1
7.5 kW10.115.514.9
11 kW14.822.021.2
15 kW20.129.028.0
18.5 kW24.835.033.7
22 kW29.541.039.5
30 kW40.256.054.0
37 kW49.668.065.5
45 kW60.383.080.0
55 kW73.8100.096.4
75 kW100.6135.0130.1
90 kW120.7160.0154.2
110 kW147.5195.0188.0
132 kW177.0230.0221.7
160 kW214.6280.0269.9
200 kW268.2350.0337.3
250 kW335.3430.0414.5

Single-phase motors, 230 V and 240 V

Full-load current (A), single-phase
Motorhp230 V240 V
0.37 kW0.503.23.1
0.55 kW0.744.64.4
0.75 kW1.015.85.6
1.1 kW1.488.07.7
1.5 kW2.0110.510.1
2.2 kW2.9514.513.9
3 kW4.0219.018.2

Common questions

How do I work out motor full-load current?

Use the nameplate figure. Without it, three-phase current is roughly kW × 1000 ÷ (√3 × 400 × efficiency × power factor). The chart gives typical values for 4-pole motors.

What is the full-load current of an 11 kW motor?

About 22.0 A at 400 V for a typical 4-pole motor.

What supply voltages does it use?

230 V and 240 V single-phase, and 400 V and 415 V three-phase. 230/400 V is the nominal voltage in AS 60038; many sites and nameplates still quote 240/415 V.

Need it installed? Speak with our team.

We install motors, pumps, conveyors and machinery across Sydney. Send through the details and we will provide a quotation.

Office · rapid breakdown response

02 7228 4788

Director · Stuartstuart@sydneyengineering.au