Motor full-load current chart
Typical full-load amps for 4-pole induction motors at 400 V and 415 V three-phase and 230 V and 240 V single-phase. Use the calculator above the chart to go straight from motor size to cable size.
For estimating purposes only. Results are indicative. Final selections must be confirmed by a qualified person for the actual installation and conditions.
1 The load
Star-delta needs two cables to the motor (six cores). Each carries 58% of full-load current.
2 The cable
3 Installation and run
4 Protection optional
The MCB sets the earth fault loop length check (loop impedance at 80% of nominal voltage). Fault level and clearing time set the short-circuit check.
Results are indicative estimates for planning only and must be checked by a qualified person. Read the calculator disclaimer.
Three-phase motors, 400 V and 415 V
Typical 4-pole motors. Always use the nameplate current where you have it.
| Motor | hp | 400 V | 415 V |
|---|---|---|---|
| 0.37 kW | 0.5 | 1.1 | 1.1 |
| 0.55 kW | 0.7 | 1.5 | 1.4 |
| 0.75 kW | 1.0 | 1.9 | 1.8 |
| 1.1 kW | 1.5 | 2.6 | 2.5 |
| 1.5 kW | 2.0 | 3.4 | 3.3 |
| 2.2 kW | 3.0 | 4.9 | 4.7 |
| 3 kW | 4.0 | 6.5 | 6.3 |
| 4 kW | 5.4 | 8.5 | 8.2 |
| 5.5 kW | 7.4 | 11.5 | 11.1 |
| 7.5 kW | 10.1 | 15.5 | 14.9 |
| 11 kW | 14.8 | 22.0 | 21.2 |
| 15 kW | 20.1 | 29.0 | 28.0 |
| 18.5 kW | 24.8 | 35.0 | 33.7 |
| 22 kW | 29.5 | 41.0 | 39.5 |
| 30 kW | 40.2 | 56.0 | 54.0 |
| 37 kW | 49.6 | 68.0 | 65.5 |
| 45 kW | 60.3 | 83.0 | 80.0 |
| 55 kW | 73.8 | 100.0 | 96.4 |
| 75 kW | 100.6 | 135.0 | 130.1 |
| 90 kW | 120.7 | 160.0 | 154.2 |
| 110 kW | 147.5 | 195.0 | 188.0 |
| 132 kW | 177.0 | 230.0 | 221.7 |
| 160 kW | 214.6 | 280.0 | 269.9 |
| 200 kW | 268.2 | 350.0 | 337.3 |
| 250 kW | 335.3 | 430.0 | 414.5 |
Single-phase motors, 230 V and 240 V
| Motor | hp | 230 V | 240 V |
|---|---|---|---|
| 0.37 kW | 0.50 | 3.2 | 3.1 |
| 0.55 kW | 0.74 | 4.6 | 4.4 |
| 0.75 kW | 1.01 | 5.8 | 5.6 |
| 1.1 kW | 1.48 | 8.0 | 7.7 |
| 1.5 kW | 2.01 | 10.5 | 10.1 |
| 2.2 kW | 2.95 | 14.5 | 13.9 |
| 3 kW | 4.02 | 19.0 | 18.2 |
More cable tools
Worked tables for common motors at 400 V and 415 V, plus reference charts.
- Cable size for a 5.5 kW motor
- Cable size for a 7.5 kW motor
- Cable size for an 11 kW motor
- Cable size for a 15 kW motor
- Cable size for a 22 kW motor
- Cable size for a 30 kW motor
- Cable size for a 37 kW motor
- Cable size for a 45 kW motor
- Cable size for a 55 kW motor
- Cable size for a 75 kW motor
- Cable size calculator by amps
- Motor full-load current chart
- Cable voltage drop calculator
More free tools
Cylinder and tank volume calculator
Litres and m³ for round, horizontal and rectangular tanks, pipe and hoppers, full or part full.
Open tool →MechanicalBolt torque calculator
Metric bolts M6 to M48, any grade and thread condition, with flange tightening sequences.
Open tool → All toolsEvery calculator and chart
Tank and pipe volumes, cable sizing, bolt torque and flange tightening in one place.
See all →Common questions
How do I work out motor full-load current?
Use the nameplate figure. Without it, three-phase current is roughly kW × 1000 ÷ (√3 × 400 × efficiency × power factor). The chart gives typical values for 4-pole motors.
What is the full-load current of an 11 kW motor?
About 22.0 A at 400 V for a typical 4-pole motor.
What supply voltages does it use?
230 V and 240 V single-phase, and 400 V and 415 V three-phase. 230/400 V is the nominal voltage in AS 60038; many sites and nameplates still quote 240/415 V.
Need it installed? Speak with our team.
We install motors, pumps, conveyors and machinery across Sydney. Send through the details and we will provide a quotation.