Cable voltage drop calculator
Check the voltage drop on a run and find the smallest cable that keeps it under your limit. Size by amps or from a motor, single-phase or three-phase, copper or aluminium.
For estimating purposes only. Results are indicative. Final selections must be confirmed by a qualified person for the actual installation and conditions.
1 The load
Star-delta needs two cables to the motor (six cores). Each carries 58% of full-load current.
2 The cable
3 Installation and run
4 Protection optional
The MCB sets the earth fault loop length check (loop impedance at 80% of nominal voltage). Fault level and clearing time set the short-circuit check.
Results are indicative estimates for planning only and must be checked by a qualified person. Read the calculator disclaimer.
Voltage drop, rating and earth by cable size
Copper multicore, three-phase. Ratings at 40 °C air, calculated from first principles. Earth full size to 16 mm², then at least one-third of the active.
| Size | PVC mV/A/m | XLPE mV/A/m | XLPE on tray, 40 °C (A) | PVC in conduit, 40 °C (A) | Earth mm² |
|---|---|---|---|---|---|
| 1.5 mm² | 25.68 | 26.93 | 18 | 13 | 1.5 |
| 2.5 mm² | 15.41 | 16.16 | 25 | 18 | 2.5 |
| 4 mm² | 9.63 | 10.1 | 33 | 23 | 4 |
| 6 mm² | 6.42 | 6.73 | 42 | 29 | 6 |
| 10 mm² | 3.86 | 4.04 | 57 | 39 | 10 |
| 16 mm² | 2.41 | 2.53 | 78 | 51 | 16 |
| 25 mm² | 1.55 | 1.62 | 102 | 66 | 10 |
| 35 mm² | 1.11 | 1.16 | 127 | 81 | 16 |
| 50 mm² | 0.78 | 0.82 | 161 | 100 | 25 |
| 70 mm² | 0.57 | 0.59 | 199 | 122 | 25 |
| 95 mm² | 0.43 | 0.44 | 243 | 146 | 35 |
| 120 mm² | 0.35 | 0.36 | 283 | 167 | 50 |
| 150 mm² | 0.29 | 0.3 | 330 | – | 50 |
| 185 mm² | 0.25 | 0.25 | 378 | – | 70 |
| 240 mm² | 0.21 | 0.21 | 449 | – | 95 |
| 300 mm² | 0.18 | 0.18 | 519 | – | 120 |
How the calculator works
Two calculators, one method. Pick Motor circuit to start from kW or hp, or General circuit to start from amps, kW or kVA.
1. Load current. Motor circuits use the typical full-load current of a 4-pole motor at the selected voltage, or your nameplate figure, with an optional 25% margin. Star-delta splits it across two cables at 58% each. General circuits use the amps you enter, or work them out from kW and power factor, or kVA.
2. Current-carrying capacity (heat balance). The rating is worked out from the conductor’s losses (I²R at operating temperature) against the thermal resistance of the insulation, sheath and surroundings for the installation method, at the ambient you enter, then reduced for grouping and compared with the design current. Parallel cables share the load and count toward grouping.
Voltage drop % = mV/A/m × I × L ÷ 1000 ÷ V × 100
3. Voltage drop (resistance and reactance at operating temperature, 5% limit per AS/NZS 3000). Checked against your limit, 5% by default. If it fails, the next size up is tried and the tool tells you voltage drop set the size.
4. Protection (optional). With an MCB entered, the tool checks IB ≤ IN ≤ IZ and the maximum route length for automatic disconnection from the loop impedance at 80% of nominal voltage. With a fault level and clearing time, it checks the active conductor can survive the fault (S ≥ I√t ÷ k).
Lmax = 0.8 × Uo × Sph × Spe ÷ (ρ × Ia × (Sph + Spe))
5. Earth conductor. Full size up to 16 mm², then at least one-third of the active size, rounded up to a standard size.
The smallest cable that passes every check is picked, and the sizes either side are shown so you can see why. Ratings are calculated from first principles for estimating purposes only.
More free tools
Cylinder and tank volume calculator
Litres and m³ for round, horizontal and rectangular tanks, pipe and hoppers, full or part full.
Open tool →MechanicalBolt torque calculator
Metric bolts M6 to M48, any grade and thread condition, with flange tightening sequences.
Open tool → All toolsEvery calculator and chart
Tank and pipe volumes, cable sizing, bolt torque and flange tightening in one place.
See all →Common questions
How do you calculate voltage drop?
Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1000. Divide by the supply voltage for a percentage.
What is the maximum voltage drop in Australia?
AS/NZS 3000 Clause 3.6.2 allows 5% from the point of supply to the load, unless a lower figure is needed for the equipment.
How does this cable calculator work?
It works from first principles: conductor resistance at operating temperature, a heat-balance current rating for the installation method with ambient temperature and grouping, voltage drop from resistance and reactance against the 5% limit in AS/NZS 3000, protection coordination, earth size, earth fault loop length and the adiabatic short-circuit check. It is for estimating purposes only, so a licensed electrician must confirm the final design.
Need it installed? Speak with our team.