Cable size for a 22 kW motor

A 22 kW motor draws about 41.0 A at 400 V, or 39.5 A at 415 V. Over 50 m on tray, DOL, that is typically 10 mm² Cu 3C+E XLPE (X-90) at either voltage. Tables for both voltages are below; change the run, method or start in the calculator for your job.

For estimating purposes only. Results are indicative. Final selections must be confirmed by a qualified person for the actual installation and conditions.

FreeNo loginNo watermark

1  The load

Starting method

2  The cable

3  Installation and run

4  Protection optional

The MCB sets the earth fault loop length check (loop impedance at 80% of nominal voltage). Fault level and clearing time set the short-circuit check.

Results are indicative estimates for planning only and must be checked by a qualified person. Read the calculator disclaimer.

22 kW motor cable sizes at 400 V

Copper multicore, 40 °C air, one circuit, 5% voltage drop limit, sized at 125% of full-load current. Voltage drop in brackets. 400 V is the nominal three-phase voltage in AS 60038.

Minimum cable size by run length, 400 V three-phase
Start and install10 m25 m50 m75 m100 m150 m
DOL, XLPE on tray10 mm² (0.4%)10 mm² (1.0%)10 mm² (2.1%)10 mm² (3.1%)10 mm² (4.1%)16 mm² (3.9%)
VSD, XLPE on tray10 mm² (0.4%)10 mm² (1.0%)10 mm² (2.1%)10 mm² (3.1%)10 mm² (4.1%)16 mm² (3.9%)
Star-delta, XLPE on tray2×6 mm² (0.4%)2×6 mm² (1.0%)2×6 mm² (2.0%)2×6 mm² (3.0%)2×6 mm² (4.0%)2×10 mm² (3.6%)
DOL, PVC in conduit16 mm² (0.2%)16 mm² (0.6%)16 mm² (1.2%)16 mm² (1.9%)16 mm² (2.5%)16 mm² (3.7%)

22 kW motor cable sizes at 415 V

Copper multicore, 40 °C air, one circuit, 5% voltage drop limit, sized at 125% of full-load current. Voltage drop in brackets. Many sites and older nameplates still quote 415 V.

Minimum cable size by run length, 415 V three-phase
Start and install10 m25 m50 m75 m100 m150 m
DOL, XLPE on tray10 mm² (0.4%)10 mm² (1.0%)10 mm² (1.9%)10 mm² (2.9%)10 mm² (3.8%)16 mm² (3.6%)
VSD, XLPE on tray10 mm² (0.4%)10 mm² (1.0%)10 mm² (1.9%)10 mm² (2.9%)10 mm² (3.8%)16 mm² (3.6%)
Star-delta, XLPE on tray2×4 mm² (0.6%)2×4 mm² (1.4%)2×4 mm² (2.8%)2×4 mm² (4.2%)2×6 mm² (3.7%)2×10 mm² (3.3%)
DOL, PVC in conduit16 mm² (0.2%)16 mm² (0.6%)16 mm² (1.1%)16 mm² (1.7%)16 mm² (2.3%)16 mm² (3.4%)

How the calculator works

Two calculators, one method. Pick Motor circuit to start from kW or hp, or General circuit to start from amps, kW or kVA.

1. Load current. Motor circuits use the typical full-load current of a 4-pole motor at the selected voltage, or your nameplate figure, with an optional 25% margin. Star-delta splits it across two cables at 58% each. General circuits use the amps you enter, or work them out from kW and power factor, or kVA.

2. Current-carrying capacity (heat balance). The rating is worked out from the conductor’s losses (I²R at operating temperature) against the thermal resistance of the insulation, sheath and surroundings for the installation method, at the ambient you enter, then reduced for grouping and compared with the design current. Parallel cables share the load and count toward grouping.

Voltage drop % = mV/A/m × I × L ÷ 1000 ÷ V × 100

3. Voltage drop (resistance and reactance at operating temperature, 5% limit per AS/NZS 3000). Checked against your limit, 5% by default. If it fails, the next size up is tried and the tool tells you voltage drop set the size.

4. Protection (optional). With an MCB entered, the tool checks IB ≤ IN ≤ IZ and the maximum route length for automatic disconnection from the loop impedance at 80% of nominal voltage. With a fault level and clearing time, it checks the active conductor can survive the fault (S ≥ I√t ÷ k).

Lmax = 0.8 × Uo × Sph × Spe ÷ (ρ × Ia × (Sph + Spe))

5. Earth conductor. Full size up to 16 mm², then at least one-third of the active size, rounded up to a standard size.

The smallest cable that passes every check is picked, and the sizes either side are shown so you can see why. Ratings are calculated from first principles for estimating purposes only.

Common questions

What size cable for a 22 kW motor?

A 22 kW motor draws about 41.0 A at 400 V or 39.5 A at 415 V. For a 50 m DOL run on tray in XLPE, the estimate is 10 mm² Cu 3C+E XLPE (X-90). Longer runs need a larger cable for voltage drop.

What is the full-load current of a 22 kW motor?

About 41.0 A at 400 V and 39.5 A at 415 V for a typical 4-pole motor. Use the nameplate figure where you have it.

Does 400 V or 415 V change the cable size?

Rarely. At 415 V the current is about 3.5% lower and the voltage drop percentage slightly lower, so a cable only drops a size on runs right at the voltage drop limit.

How does this cable calculator work?

It works from first principles: conductor resistance at operating temperature, a heat-balance current rating for the installation method with ambient temperature and grouping, voltage drop from resistance and reactance against the 5% limit in AS/NZS 3000, protection coordination, earth size, earth fault loop length and the adiabatic short-circuit check. It is for estimating purposes only, so a licensed electrician must confirm the final design.