Cable size calculator by amps
Enter the load in amps, kW or kVA, how the cable is run and, if you know it, the breaker. The calculator finds the smallest copper or aluminium cable that passes current rating, voltage drop, earth fault loop length and fault rating checks.
For estimating purposes only. Results are indicative. Final selections must be confirmed by a qualified person for the actual installation and conditions.
1 The load
Star-delta needs two cables to the motor (six cores). Each carries 58% of full-load current.
2 The cable
3 Installation and run
4 Protection optional
The MCB sets the earth fault loop length check (loop impedance at 80% of nominal voltage). Fault level and clearing time set the short-circuit check.
Results are indicative estimates for planning only and must be checked by a qualified person. Read the calculator disclaimer.
How the calculator works
Two calculators, one method. Pick Motor circuit to start from kW or hp, or General circuit to start from amps, kW or kVA.
1. Load current. Motor circuits use the typical full-load current of a 4-pole motor at the selected voltage, or your nameplate figure, with an optional 25% margin. Star-delta splits it across two cables at 58% each. General circuits use the amps you enter, or work them out from kW and power factor, or kVA.
2. Current-carrying capacity (heat balance). The rating is worked out from the conductor’s losses (I²R at operating temperature) against the thermal resistance of the insulation, sheath and surroundings for the installation method, at the ambient you enter, then reduced for grouping and compared with the design current. Parallel cables share the load and count toward grouping.
Voltage drop % = mV/A/m × I × L ÷ 1000 ÷ V × 100
3. Voltage drop (resistance and reactance at operating temperature, 5% limit per AS/NZS 3000). Checked against your limit, 5% by default. If it fails, the next size up is tried and the tool tells you voltage drop set the size.
4. Protection (optional). With an MCB entered, the tool checks IB ≤ IN ≤ IZ and the maximum route length for automatic disconnection from the loop impedance at 80% of nominal voltage. With a fault level and clearing time, it checks the active conductor can survive the fault (S ≥ I√t ÷ k).
Lmax = 0.8 × Uo × Sph × Spe ÷ (ρ × Ia × (Sph + Spe))
5. Earth conductor. Full size up to 16 mm², then at least one-third of the active size, rounded up to a standard size.
The smallest cable that passes every check is picked, and the sizes either side are shown so you can see why. Ratings are calculated from first principles for estimating purposes only.
More cable tools
Worked tables for common motors at 400 V and 415 V, plus reference charts.
- Cable size for a 5.5 kW motor
- Cable size for a 7.5 kW motor
- Cable size for an 11 kW motor
- Cable size for a 15 kW motor
- Cable size for a 22 kW motor
- Cable size for a 30 kW motor
- Cable size for a 37 kW motor
- Cable size for a 45 kW motor
- Cable size for a 55 kW motor
- Cable size for a 75 kW motor
- Cable size calculator by amps
- Motor full-load current chart
- Cable voltage drop calculator
More free tools
Cylinder and tank volume calculator
Litres and m³ for round, horizontal and rectangular tanks, pipe and hoppers, full or part full.
Open tool →MechanicalBolt torque calculator
Metric bolts M6 to M48, any grade and thread condition, with flange tightening sequences.
Open tool → All toolsEvery calculator and chart
Tank and pipe volumes, cable sizing, bolt torque and flange tightening in one place.
See all →Common questions
What size cable for 32 A?
It depends on the run and installation. Over 30 m on tray at 40 °C, a 32 A three-phase circuit typically needs 4 mm² copper with a type C 32 A MCB. Use the calculator for your run.
How does this cable calculator work?
It works from first principles: conductor resistance at operating temperature, a heat-balance current rating for the installation method with ambient temperature and grouping, voltage drop from resistance and reactance against the 5% limit in AS/NZS 3000, protection coordination, earth size, earth fault loop length and the adiabatic short-circuit check. It is for estimating purposes only, so a licensed electrician must confirm the final design.
What supply voltages does it use?
230 V and 240 V single-phase, and 400 V and 415 V three-phase. 230/400 V is the nominal voltage in AS 60038; many sites and nameplates still quote 240/415 V.
What voltage drop is allowed?
AS/NZS 3000 allows 5% from the point of supply to the load. If the submains already use some of that, set a lower limit for the final circuit.
When should a cable run be professionally designed?
Long runs, large motors, large VSDs, high temperatures, grouped underground cables, high fault levels, or anywhere discrimination and protection settings matter. The tool flags these.